Abstract
A time constant including building geometry and design fire characteristics was suggested for specifying smoke filling in atria. From the survey results on 138 local atria, time constants of 73 atria were calculated. The smoke filling times required to fill 80 % of the space volume were evaluated from the NFPA smoke filling equation with a slow t2-fire. The time for the smoke front to reach the ceiling was taken into account. It is further confirmed that time constant is a better parameter than the space volume used in the current fire codes, and is thus recommended to the Authority.
Original language | English |
---|---|
Pages (from-to) | 58-60 |
Number of pages | 3 |
Journal | International journal on engineering performance-based fire codes |
Volume | 2 |
Issue number | 2 |
Publication status | Published - 2000 |