Abstract
Analysis of lightning current in communication and power cables is essential for lightning protection in radio base stations. In this paper an equivalent circuit method is developed to evaluate lightning current distribution among the cables mounted on a cable ladder. Both skin and proximity effects in the cables are taken into account and an efficient modelling procedure is presented. The proposed method is validated experimentally, and is applied to evaluate the lightning current in a practical cable installation. A significant error is observed if the traditional model is used.
Original language | English |
---|---|
Title of host publication | 2014 International Conference on Lightning Protection, ICLP 2014 |
Publisher | IEEE |
Pages | 412-417 |
Number of pages | 6 |
ISBN (Electronic) | 9781479935444 |
DOIs | |
Publication status | Published - 1 Jan 2014 |
Event | 2014 International Conference on Lightning Protection, ICLP 2014 - Crowne Plaza Shanghai, Shanghai, China Duration: 11 Oct 2014 → 18 Oct 2014 |
Conference
Conference | 2014 International Conference on Lightning Protection, ICLP 2014 |
---|---|
Country/Territory | China |
City | Shanghai |
Period | 11/10/14 → 18/10/14 |
Keywords
- cable
- lightning current
- PEEC
- proximity effect
- skin effect
ASJC Scopus subject areas
- Environmental Engineering