Abstract
This paper highlights the importance of proper initialization techniques for simulation model stability and computational efficiency of multi-terminal direct current (MTDC) systems. A steady-state approach is presented for initializing grid-forming voltage source converters (GVSCs). Moreover, for black-box GVSC models, a generic initialization method, called decoupling interface (DI) is proposed. The method is tested on the CIGRE BM4 benchmark using EMTP. Compared to an existing load-flow initialization technique, both initialization methods reduce the complete system initialization time by 6.9 times.
| Original language | English |
|---|---|
| Article number | 110674 |
| Pages (from-to) | 1-6 |
| Number of pages | 6 |
| Journal | Electric Power Systems Research |
| Volume | 235 |
| DOIs | |
| Publication status | Published - Oct 2024 |
Keywords
- EMT
- HVDC
- Initialization
- MTDC
- Offline simulation
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering