Abstract
Full-scale burning tests on studying the suppression of Poly(methyl methacrylate) (PMMA) fires using water mists are reported in this paper. The water mists were generated from a single fluid nozzle operating at low pressures of up to 0.8 MPa. The flame suppression processes were observed and analyzed using a Charge Coupled Device (CCD) video camera. Experiments were carried out under the exhaust hood of a fan-duct system in an oxygen consumption calorimeter. Results indicated that PMMA fires could be suppressed effectively using this low-pressure water mist system. For this small PMMA fire, fuel surface cooling is further confirmed to be the key extinguishing mechanism. The production rate of smoke and toxic gases, including carbon monoxide, would also be reduced. The total extinguishment time can be divided into flame knocked-down time and ghost flame existing time for better evaluating the suppression performance. Increasing the operating pressure of the water mist system would give shorter ghost flame existing times and hence faster fire extinguishment. Results on water mist characteristics and fire behavior, such as heat release rate, are useful for modeling fire suppression.
Original language | English |
---|---|
Pages (from-to) | 32-39 |
Number of pages | 8 |
Journal | Fire Safety Journal |
Volume | 47 |
DOIs | |
Publication status | Published - 1 Jan 2012 |
Keywords
- Fire suppression
- Oxygen consumption calorimeter
- PMMA
- Water mist
ASJC Scopus subject areas
- General Chemistry
- General Materials Science
- Safety, Risk, Reliability and Quality
- General Physics and Astronomy