Evaluation of the Guang Dong lightning location system with transmission line fault data

S. M. Chen, Ya Ping Du, L. M. Fan, H. M. He, D. Z. Zhong

Research output: Journal article publicationJournal articleAcademic researchpeer-review

30 Citations (Scopus)

Abstract

The Guang Dong lightning location system (GDLLS) was put into operation in 1997. Its performance, including detection efficiency and location accuracy, was evaluated with the data of the recorded lightning faults on 110, 220 and 500 kV transmission lines in 1997-1999. Lightning parameters, such as thunderstorm days, ground-flash density and peak lightning current were estimated with the lightning data collected by GDLLS. It is found that the detection efficiency is as high as 86%, and the median lightning accuracy is about 1.3 km. The correlation between the number of detected lightning flashes and recorded transmission line faults is weak, but can be improved if more appropriate analysis methods or data are employed.
Original languageEnglish
Pages (from-to)9-16
Number of pages8
JournalIEE Proceedings: Science, Measurement and Technology
Volume149
Issue number1
DOIs
Publication statusPublished - 1 Jan 2002

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Evaluation of the Guang Dong lightning location system with transmission line fault data'. Together they form a unique fingerprint.

Cite this