Cool storage performance of integrated heat pump system with triple-sleeve energy storage exchanger

Fuxin Niu, Long Ni, Yang Yao, Shiming Deng

Research output: Journal article publicationConference articleAcademic researchpeer-review

5 Citations (Scopus)

Abstract

A new integrated heat pump system with triple-sleeve energy storage exchanger was proposed. Experimental system was designed and developed. The cool storage performance of integrated system was studied. The results showed that evaporating temperature was 1? which was higher than ice storage. COP of cool storage process at the highest point 2.4 dropped to 1.75. In general, system efficiency kept a high level.
Original languageEnglish
Pages (from-to)1896-1902
Number of pages7
JournalEnergy Procedia
Volume14
DOIs
Publication statusPublished - 22 Mar 2012
Event2011 2nd International Conference on Advances in Energy Engineering, ICAEE 2011 - Bangkok, Thailand
Duration: 27 Dec 201128 Dec 2011

Keywords

  • Cool storage
  • Heat pump
  • Integrated system
  • Triple-sleeve

ASJC Scopus subject areas

  • General Energy

Fingerprint