Application Feasibility of Passive Radiative Cool Paint on a Stand-Alone Data Center with Adjacent Buildings

Yin Hoi Chan, Yi Fan Wang, Ka Chung Chan, Kaixin Lin, Tsz Chung Ho, Chi Yan Tso, Christopher Yu Hang Chao, Sau Chung Fu

Research output: Chapter in book / Conference proceedingConference article published in proceeding or bookAcademic researchpeer-review

Abstract

Unlike typical buildings that require outdoor scenic view, data centers are un-fenestrated facilities for minimizing access vulnerability and preventing unauthorized admission. As a result, data centers provide expansive surface for radiative cooler application. The energy-saving potential of a radiative cool paint on a high-rise data center was explored using a self-created site model. The east-facing wall that received the most solar radiation among the five facets obtained the highest savings in both unshaded and shaded cases. The performance of the cool paint was further improved, and outstanding cooling power of 27–30 W/m2 was achieved when the cool paint was applied to both roof and walls of the data center. Moreover, this study adopted the cool paint to three different sections of the data center (lower, middle and upper) in respective cases. It was discovered that the cooling effect reduced with increasing altitude in the unshaded cases, whereas it was inconsistently affected by the presence of adjacent shading objects that have different heights in the shaded cases.

Original languageEnglish
Title of host publicationProceedings of 2024 International Conference on Energy Engineering - Volume II
EditorsLin Vivien Lu
PublisherSpringer Science and Business Media Deutschland GmbH
Pages55-59
Number of pages5
ISBN (Print)9789819664436
DOIs
Publication statusE-pub ahead of print - 27 May 2025
EventInternational Conference on Energy Engineering, ICEE 2024 - Hong Kong, China
Duration: 29 Nov 20242 Dec 2024

Publication series

NameLecture Notes in Electrical Engineering
Volume1426 LNEE
ISSN (Print)1876-1100
ISSN (Electronic)1876-1119

Conference

ConferenceInternational Conference on Energy Engineering, ICEE 2024
Country/TerritoryChina
CityHong Kong
Period29/11/242/12/24

Keywords

  • Building Energy Saving
  • Data center
  • Passive Cooling

ASJC Scopus subject areas

  • Industrial and Manufacturing Engineering

Fingerprint

Dive into the research topics of 'Application Feasibility of Passive Radiative Cool Paint on a Stand-Alone Data Center with Adjacent Buildings'. Together they form a unique fingerprint.