A simplified model for counterflow internally cooled/heated dehumidifier/regenerator in liquid desiccant dehumidification system

Ronghui Qi, Lin Lu, Hongxing Yang

Research output: Chapter in book / Conference proceedingConference article published in proceeding or bookAcademic researchpeer-review

Abstract

This paper developed a new simplified model for counterflow internally cooled/heated dehumidifier/regenerator (ICHDR) in liquid desiccant air conditioning system, by introducing three efficiencies, i.e. efficiency of air temperature, efficiency of air moisture content and efficiency of fluid temperature. Empirical formulas of these efficiencies, considering the influences of inlet parameters of all fluids and system configuration parameters, were developed by numerical simulation. Results show that the differences between the simplified model and mathematical model of ICHDR are within ±20%, with a mean absolute error less than 10%. With this simplified model, outlet parameters of the dehumidifier/regenerator could be easily gained by the set parameters. The developed model can be used for many applications, especially the dynamic performance simulation of the system.
Original languageEnglish
Title of host publication10th International Conference on Healthy Buildings 2012
Pages1925-1930
Number of pages6
Volume3
Publication statusPublished - 1 Dec 2012
Event10th International Conference on Healthy Buildings 2012 - Brisbane, QLD, Australia
Duration: 8 Jul 201212 Jul 2012

Conference

Conference10th International Conference on Healthy Buildings 2012
Country/TerritoryAustralia
CityBrisbane, QLD
Period8/07/1212/07/12

Keywords

  • Dehumidification
  • Efficiency
  • Emprical formula
  • Simplified model
  • Simulation

ASJC Scopus subject areas

  • Civil and Structural Engineering

Fingerprint