Abstract
The fixture unit approach with an arbitrarily assumed reference flow rate is commonly used for the estimation of probable maximum simultaneous demand in many building water systems. This study evaluates such estimations for some high-rise buildings in terms of various reference flow rates. The estimation accuracies are analysed against Monte Carlo simulations with which no reference flow rate is assumed. The results reveal that the traditionally assumed reference flow rate (10 lℓ·s-1) for demand analysis should be increased to 250 ℓ·s-1 for high-rise water systems in a dense built environment similar to Hong Kong.
Original language | English |
---|---|
Pages (from-to) | 109-114 |
Number of pages | 6 |
Journal | Water SA |
Volume | 37 |
Issue number | 1 |
Publication status | Published - 1 Jan 2011 |
Keywords
- Demand analysis
- Fixture unit approach
- Reference flow rate
- Water supply system
ASJC Scopus subject areas
- Water Science and Technology
- Management, Monitoring, Policy and Law
- Applied Microbiology and Biotechnology
- Waste Management and Disposal